Sign In | Join Free | My himfr.com
Home > Perkins Diesel Generator >

3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S

    Buy cheap 3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S from wholesalers
     
    Buy cheap 3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S from wholesalers
    • Buy cheap 3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S from wholesalers
    • Buy cheap 3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S from wholesalers

    3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S

    Ask Lasest Price
    Brand Name : GSKA
    Model Number : JP-P33E1
    Price : Negotiable
    Delivery Time : 3-5 days on receipt of official sales contract
    Payment Terms : L/C,D/P,D/A, Alipay, West Union, TT. Cash,Paypal
    Supply Ability : 500 pieces per Month
    • Product Details
    • Company Profile

    3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S


    1. Standby power: 26.4 kw

    2.Engine Make & Model: Perkins 1103A-33G1

    3.Alternator Model: LL1014S

    4.Base Frame Type: Heavy Duty FabriCAT-parts-partsed Steel

    5.Circuit Breaker Type: 3 Pole MCB

    6.Cooling Method: Water Governing

    7.Type: Mechanical Governing

    10.Class: ISO 8528 G2

    11.Compression Ratio: 19.25:1

    12.Displacement: l (cu.in) 3.3 (201.4)

    13.Bore/Stroke: mm (in) 105.0 (4.1)/127.0 (5.0)

    14.Moment of Inertia: kg m² (lb. in²) 1.14


    3 Cylinders Perkins Diesel Generator , 1103A-33G1 , LL1014S


    Output Ratings

    Generating Set Model

    * JPP33E1

    Prime* Standby*

    380-415V, 50 Hz

    30.0 kVA 33.0 kVA

    24.0 kW 26.4 kW

    480V, 60 Hz

    33.8 kVA 37.5 kVA

    27.0 kW 30.0 kW

    • Refer to ratings definitions on page 4.

    Ratings at 0.8 power factor.


    Technical Data

    Engine Make & Model:

    Perkins 1103A-33G1

    Alternator Model:

    LL1014S

    Base Frame Type:

    Heavy Duty FabriCAT-parts-partsed Steel

    Circuit Breaker Type:

    3 Pole MCB

    Frequency:

    50 Hz 60 Hz

    Engine Speed: RPM

    1500 1800

    Fuel Tank Capacity: litres (US gal)

    144 (38.0)

    Fuel Consumption: P30P1 l/hr (US gal/hr)

    6.9 (1.8) 8.0 (2.1)

    Fuel Consumption: P33E1 l/hr (US gal/hr)

    7.6 (2.0) 8.9 (2.4)

    P30P1 / P33E1


    Engine Technical Data


    Physical Data

    Manufacturer: Perkins

    Model: 1103A-33G1

    No. of Cylinders/Alignment: 3 / In Line

    Cycle: 4 Stroke

    Induction: Naturally Aspirated

    Cooling Method: Water Governing

    Type: Mechanical Governing

    Class: ISO 8528 G2

    Compression Ratio: 19.25:1

    Displacement: l (cu.in) 3.3 (201.4)

    Bore/Stroke: mm (in) 105.0 (4.1)/127.0 (5.0)

    Moment of Inertia: kg m² (lb. in²) 1.14 (3896)

    Engine Electrical System:

    -Voltage/Ground: 12/Negative

    -Battery Charger Amps: 65

    Weight: kg (lb) - Dry: 412 (908)

    - Wet: 430 (948)


    Air System 50 Hz 60 Hz


    Air Filter Type: Replaceable

    Element Combustion Air Flow:m³/min (cfm)

    -Standby: 2.5 (88) 3.0 (106)

    -Prime: 2.5 (88) 2.9 (102)

    Max. Combustion Air Intake

    Restriction: kPa (in H2O) 6.5 (26.1) 6.5 (26.1)

    Radiator Cooling Air Flow:

    m³/min (cfm) 69.6 (2458) 90.6 (3200)

    External Restriction to Cooling Air Flow: Pa (in H2O) 120 (0.5) 120 (0.5)


    Cooling System 50 Hz 60 Hz

    Cooling System Capacity: l (US gal) 10.2 (2.7) 10.2 (2.7)

    Water Pump Type: Centrifugal

    Heat Rejected to Water & Lube Oil: kW (Btu/min)

    -Standby: 15.2 (864) 21.6 (1228)

    -Prime: 13.6 (773) 19.2 (1092)

    Heat Radiation to Room: kW (Btu/min)

    -Standby: 9.2 (523) 9.7 (552)

    -Prime: 8.2 (466) 8.4 (478)

    Radiator Fan Load: kW (hp) 0.3 (0.4) 0.5 (0.7)

    Cooling system designed to operate in ambient conditions up to 50°C (122°F).


    Performance 50 Hz 60 Hz

    Engine Speed: RPM 1500 1800

    Gross Engine Power: kW (hp)

    -Standby: 31.0 (42.0) 36.5 (49.0)

    -Prime: 28.2 (38.0) 33.1 (44.0)

    BMEP: kPa (psi)

    -Standby: 752.0 (109.0) 738.0 (107.0)

    -Prime: 684.0 (99.2) 669.0 (97.0)

    Regenerative Power: kW 7.0 9.0


    LubriCAT-parts-partsion System


    Oil Filter Type: Spin-On, Full Flow

    Total Oil Capacity l (US gal): 8.3 (2.2)

    Oil Pan l (US gal): 7.8 (2.1)

    Oil Type: AP1 CG4 15W-40

    Cooling Method: Water


    Fuel System

    Fuel Filter Type: Replaceable

    Element Recommended Fuel: Class A2 Diesel

    Fuel Consumption: l/hr (US gal/hr)

    110% 100% 75% 50%

    Load Load Load Load

    P30P1


    50 Hz 7.6 (2.0) 6.9 (1.8) 5.2 (1.4) 3.8 (1.0)

    60 Hz 8.9 (2.4) 8.0 (2.1) 6.2 (1.6) 4.7 (1.2)

    P33E1


    50 Hz 7.6 (2.0) 5.7 (1.5) 4.1 (1.1)

    60 Hz 8.9 (2.4) 6.8 (1.8) 5.0 (1.3)


    (based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)


    Exhaust System 50 Hz 60 Hz

    Silencer Type: Level 1

    Silencer Model & Qty: SD50 (1) Pressure Drop Across

    Silencer System: kPa (in Hg) 1.80 (0.532) 2.00 (0.591)

    Silencer Noise Reduction

    Level: dB 20 19

    Max. Allowable Back

    Pressure: kPa (in. Hg) 15.0 (4.4) 15.0 (4.4)

    Exhaust Gas Flow:

    m³/min (cfm) -Standby: 6.2 (219) 7.5 (265)

    -Prime: 5.2 (184) 6.3 (222)

    Exhaust Gas Temperature: °C (°F)

    m³/min (cfm) -Standby: 490 (914) 510 (950)

    -Prime: 472 (882) 501 (934)

    P30P1 / P33E1


    Alternator Performance Data



    Data Item

    50 Hz 60 Hz

    415/240V

    400/230V

    230/115V

    200/115V

    380/220V

    220/110V

    220/127V

    480/277V

    240/139V

    380/220V

    220/110V

    240/120V

    208/120V

    230/115V

    440/254V

    220/127V


    Motor Starting Capability* kVA


    64


    60


    55


    71


    70


    47


    55


    52


    61


    Short Circuit Capacity** %


    0


    0


    0


    0


    0


    0


    0


    0


    0


    Reactances: Per Unit


    Xd X'd X''d


    1.970


    0.100


    0.052


    2.120


    0.110


    0.056


    2.350


    0.120


    0.062


    1.750


    0.090


    0.046


    1.990


    0.110


    0.053


    3.170


    0.170


    0.084


    2.650


    0.140


    0.070


    2.860


    0.150


    0.076


    2.370


    0.130


    0.063


    Reactances shown are applicable to prime ratings

    • Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.

    ** With optional Permanent Magnet generator or AREP excitation.


    Alternator Technical Data


    Physical Data Operating Data

    Manufacturer: FG WILSON

    Overspeed: RPM 2250

    Model: LL1014S

    Voltage Regulation (steady state) (%): + /- 0.5

    No. of Bearings: 1

    Wave Form NEMA = TIF: 50

    Insulation Class: H

    Wave Form IEC = THF: 2.0%

    Winding Pitch Code: 2/3 - 6

    Total Harmonic Content LL/LN:4.0%

    Wires: 12

    Supression is in line with European Standard

    Radio Interference: EN61000-6

    Ingress Protection Rating: IP23

    Radiant Heat: kW (Btu/min)

    -50 Hz 3.3 (188)

    -60 Hz: 3.8 (216)

    Excitation System: SHUNT

    AVR Model: R230

    P30P1 / P33E1


    Technical Data


    3 Phase Ratings and Performance at 50 Hz, 1500 RPM

    3 Phase Ratings and Performance at 60 Hz, 1800 RPM



    Voltage Prime Model Standby Model Voltage Prime Model Standby Model

    P30P1 P33E1 P30P1 P33E1


    kVA kW

    kVA kW


    kVA kW

    kVA kW

    415/240V

    30.0 24.0

    33.0 26.4

    480/277V

    33.8 27.0

    37.5 30.0

    400/230V

    30.0 24.0

    33.0 26.4

    220/127V

    33.8 27.0

    37.5 30.0

    380/220V

    30.0 24.0

    33.0 26.4

    380/220V

    33.8 27.0

    37.4 29.9

    230/115V

    30.0 24.0

    33.0 26.4

    240/120V

    33.8 27.0

    37.5 30.0

    220/127V

    30.0 24.0

    33.0 26.4

    230/115V

    33.8 27.0

    37.5 30.0

    220/110V

    30.0 24.0

    33.0 26.4

    440/254V

    33.8 27.0

    37.5 30.0

    200/115V

    30.0 24.0

    33.0 26.4

    220/110V

    33.8 27.0

    37.4 29.9




    208/120V

    33.8 27.0

    37.5 30.0




    230/115V

    33.8 27.0

    37.5 30.0


    Definitions


    Standby Rating

    These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).



    Prime Rating

    These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.


    Standard Reference Conditions

    Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.



    Weights and Dimensions


    Weights: kg (lb) Dimensions: mm (in)



    Net (+ lube oil)


    800 (1764)


    Length


    1770 (69.7)

    Wet (+ lube oil & coolant)

    810 (1786)

    Width

    714 (28.1)

    Fuel, lube oil & coolant

    930 (2050)

    Height

    1368 (53.9)


    General Data


    Documents

    A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.


    Generating Set Standards

    The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.


    Warranty